| Place of Origin |
Zhejiang China (Mainland) |
| Model Number |
DZ47LE;C45LE |
| Type |
Earth Leakage |
| Poles Number |
3 |
Normal Operation and Mounting Requirement Circumstance temperature -5oC +40oC,average temperature not exceeding 35oC. Altitude above sea level less than 2000m. Humidity not exceeding 50% at 40oC and not exceeding 90% at 25oC. Installation class II or III. Pollution class II. Installation method DIN Rail mounting type. The external magnetism shall not be more than 5times of terrestrial one. Product shall be installed vertically at the place where there shall be no severe impact and vibration.The product is switched on when the handle is at upper position. Specifications Number of poles 1P+N, 2P, 3P, 3P+N, 4P Rated current(A)6,10,16,20,25,32,40,50,63 Rated operdting current(mA) 30,100,300,500 Rated non operating (IδN)(mA) ≤0.5Iδn Rated voltage(V) 220/380 Tripping curve C,D Type Electronic Wiring Diagram Single-PoleDouble-Pole Triple-PoleTriple-Pole Four-Pole Double Line Double LineTriple LineFour Line Four Line C45N+DZ47L C45N+DZ47LC45N+DZ47L C45N+DZ47L C45N+DZ47L C45N+C45LC45N+C45L C45N+C45L C45N+C45L C45N+C45L 1/2 2/2 3/3 3/4 4/4